Milestone: Feasibility/Design of Grey Water Heat Recovery System
This
milestone will encompass the feasibility and design of a grey water
heat recovery system for the energy efficient housing complex. A number
of different systems were analyzed. Some are currently offered for sale
commercially and others were of our own design which could be
constructed from commercially available materials. An analysis of
energy savings and economic savings was preformed to determine the
feasibility of a grey water heat recovery system for the energy
efficient housing complex.
Introduction to Grey Water Heat Recovery
Grey
water heat recovery systems utilize the energy contained in hot water
exiting the house through the drain. Many household activities, such as
showering, dishwashing, and clothes washing, allow hot water to exit
down the drain. Despite still being hot enough for use, the water is
dirty and therefore cannot be reused. A grey water heat recovery system
extracts this heat from the gray water and uses it to preheat the cold
water entering the hot water heater. figure 3.1 demonstrates how this
process works. The incoming clean water is kept separate from the grey
water to prevent contamination, but through the use of a heat exchanger
the energy stored in the grey water is transferred to the clean water.
Figure 3.1. Schematic Drawing of a Drain-water Heat Recovery System1.
There are a number
of different types of heat exchangers and grey water heat recovery
system arrangements. These arrangements depend upon the specific
application and have varying rates of efficiency. The next section will
describe some possible arrangements for energy efficient housing
complex.
Possible System Arrangements
Throughout
researching and brainstorming possible grey water heat recovery system
designs a number of possible ideas were considered. Each idea had its
own advantages and pitfalls. This sections contains a theoretically and
analytical analysis of each of this arrangements, to determine which
system would be ideal for this applicatiohl;k;ljk;jkl;xchanger would offer the highest efficiency.
Similar to figure 3.1 a coiled copper tube would be used to contain the
cold water, the
key difference between this system and the system shown in figure 3.1
is that
the coiled tube would be contained with in the drain pipe as opposed to
being
wrapped around it. An example of this system is shown in figure 3.2.

Figure 3.2. Shell and Tube Heat Exchanger Schematic.
A particular problem with a system such as this is that even when hot
water is in use (i.e. someone is taking a shower) the drain pipe is not
completely filled with grey water. The pipe is sized to handle excess
flow, thus during times of normal use there will be air and grey water
present in the pipe. This presents two problems. One, the maximum
amount of heat transfer is not occurring because the coil is not
completely surrounded by hot grey water. Two, it is impossible to
calculate the heat transfer from the grey water to the cold water.
A simple solution to this problem is to place a throttling valve at the
bottom of the drain pipe and a float switch at the top, as shown in
figure 3.2. A controller can use the throttling valve to maintain a
constant level in the pipe, monitored by the float switch. If the flow down the drain stops the last amounts of grey water will
remain in the heat exchanger until more grey water enters the drain.
This has the added advantage of allowing cold water to be heated by
grey water, even after the flow of grey water has been stopped, as
opposed to a system without a throttling valve, where the grey water
would have already left the heat exchanger.
A system such as this can be modeled using the following heat exchanger
equations, assuming the heat exchanger is perfectly insulated:
It would be wise to use these equations in a computer program because
small time steps, iterations, and solve functions are required. A
computer program was not written to model this system because more
practical reasons prevent this system from being feasible.
Placing the coiled copper tubing within the drain pipe is the ideal
location for maximum heat transfer, however over time hair, soap and
other residues will build-up causing clogging problems and preventing
efficient heat transfer. For this reason this system is not recommended
for use for this particular application.
Pure Counterflow Heat Exchanger
A single wall shell and tube pure counterflow heat exchanger is shown
in Figure 3.2. This heat exchanger operates on the same principles as
the shell and tube heat exchanger described above, but has a few
defining characteristics that separate it. As can be seen in Figure
3.2, grey water flows down through a number of smaller pipes that are
enclosed in a larger pipe which holds the incoming cold water.

Figure 3.3. Single Wall Shell and Tube Pure Counterflow Heat Exchanger.
Although this system would be less
prone to clogging than the previous, it would still encounter problems,
especially at the entrance of the system where a large drain pipe would
be split into numerous smaller ones. The major flaw of this system is
its lack of sufficient heat transfer area per unit length of pipe. The
amount of heat recovered from the grey water is directly dependent upon
the amount of heat transfer area (i.e. the area of the pipe containing
the grey water that is touching the incoming cold water). Because this
design uses straight tubing vs. coiled tubing it takes a significantly
longer pipe to achieve the same amount of heat transfer. Thus this
option becomes unfeasible and is not further addressed because it
requires too much space and adds additional capital cost.
GFX Brand Grey Water Heat Recovery Systems
GFX, an industry leader in grey water heat recovery, has developed the
system shown in figure 3.4. GFX has received Depart of Energy Grants to
research and develop this technology. After comparing this system to
the previous two listed in this report and others currently available
on the market we believe this design to offer the best performance,
reliability and value.

Figure 3.4. GFX Grey Water Heat Recovery System2.
The
previous analyses found that the best arrangement, based on pure
numbers, was a shell and tube heat exchanger. The reason why this
method could not be used was because hair and soapy water, as well as
whatever else goes down the shower drain, will cause clogging in a
shell and tube heat exchanger. One of the best features of the GFX is
that there will be no more clogging in it than any normal drain pipe.
As can be seen from figure 3.4, the GFX is also compacted, which
eliminated the problems that were encountered with a pure counter flow
heat exchanger.
GFX has many models for many different applications and loads. The
system design is also simple enough that it could be fabricated by
university personnel or students if a particular size was needed or
there was an economic benefit.
Particular Considerations
In addition to
analyzing the different systems for their own merit, considerations
have to be made for how the systems will act within the complete design
of the energy efficient housing complex.
The final design will include buildings with multiple showers, but a
single hot water heater. This presents a problem because the standard
GFX system is meant to fit one shower and one hot water heater. There
are a number of possible solutions to this problem.
One option would be to place a GFX system beneath each shower and run
the cold water coils either in series or parallel. Both of these
options present multiple problems. Running the coils in series will
result in a large pressure drop in the incoming water flow because of
the length of small diameter tubing the cold water will have to travel
through. In addition if the first GFX system is filled with hot grey
water (i.e. someone just took a shower), but the next couple of GFX
systems are filled with cool grey water (i.e. grey water left over from
a shower the previous day), the incoming cold water will be heated by
the first system and then cooled in the next couple of systems before
entering the water heater. This is obviously not very efficient.
Running the systems in parallel presents similar problems. If there are
four GFX systems per water heater, but only one of them contains hot
grey water, then three quarters of the cold water will be flowing
through inactive heat exchangers. Finally, both of these options
require an excess of materials, because a system must be placed at
every shower drain.
It is clear that if there are multiple GFX systems per water heater a
control system will need to be put in place. Control systems, and all
the plumbing for this type of operation are an added expense. To avoid
as much expense as possible, we believe a single GFX system should be
shared by multiple shower drains. As with typical residential design
philosophy the bathrooms in a single building will be located adjacent
to each other, thus the piping required to share a GFX system will not
be an issue.
In the event that the final design contains buildings with more than
four showers, it is possible that two GFX systems may need to be used.
In this case the GFX systems will be run in parallel. A differential
controller will control the flow of the incoming cold water. Thus more
cold water will be fed to the GFX system that has hotter grey water,
resulting in effectiveness equal to that of a system with one shower
and one hot water heater.
Hot Water Load
Hot water demand and use guidelines for apartment buildings are provided by ASHRAE
3.
The guidelines they give are broken into low, medium and high usage.
Medium is defined as the overall average, High is defined by tenants
that have a high percentage of children, low income, public assistance,
or no occupants working. The high category fits many characteristics of
the current University Park, but we believe University Park falls into
a slightly different category than what is intended by what ASHRAE
describes. For this reason we will take an average between the medium
and high categories to determine the hot water load per person for the
family housing complex. This data can be found in table 3.1.
Table 3.1. Hot Water Demand (Gallons per Person)3.
|
Maximum Hourly
|
Peak 15 Minutes
|
Maximum Daily
|
Average Daily
|
|
7
|
2.5
|
68.7
|
42
|
Energy Savings
A
particular hurdle in this design process was comparing how much energy
could be saved with each system. Complex heat transfer methods were
required to determine actual heat transfer from the grey water to the
cold water. These heat transfer methods are dependent upon accurate
minute by minute or even second by second hot water usage data. Because
predicting the minute by minute hot water usage data for a particular
family is very difficult, energy savings predictions are largely
dependent upon assumptions made regarding their hot water usage.
For this reason it was deemed unfeasible to try and accurately estimate
the exact energy savings provided by a GFX system. Instead calculations
were made to determine the energy savings seen when the system is under
full load (i.e. shower running, water flowing to the hot water heater
at the same flow rate as the grey water is flowing down the drain).
These numbers will give some quantity to the savings that will be
actually seen. Actual savings will depend upon the number of showers
taken and length, other hot water demand, and the effectiveness of
adding a throttling valve to the GFX system. It would be logical to
assume that the actual savings will be greater than the numbers
presented here.
Actual performance data on GFX systems is very limited. On their
website they do present effectiveness values for the G3-60 model. The
G3-60 model is a five foot long 3” drain pipe surround by
½” copper tubing. For a flow rate of two gallons per
minute, which would be typical of a low-flow showerhead, the G3-60 is
rated at about 62.5% effectiveness.
Using Equation 3.5 for this case with cold inlet water at 40° F and
grey water at 95° F, we find an energy savings of 570.6 Btu/min.
For a typical eight minute shower this would be 4564.8 Btu or 1.34 kWh.
Equation 3.5. Heat Exchanger Effectiveness
In reality what these savings
would represent for the energy efficient housing complex is hard to
quantify. If say there are 450 people living in the complex and they
take 1.25 showers per day, this would amount to a savings of 753.75
kWh. However on the electrical meter this would be an even greater
value, because conventional water heaters are not perfectly efficient.
For instance, take a typical electric water heater with an efficiency
of 90%, it would take 837.5 kWh of electricity to add the same amount
of heat as the grey water heat recovery system.
Other factors will change the results seen with this system in actual
use. As mentioned before, because of the large size of the housing
complex multiple showers will drain through the same GFX system.
Although there will not be a large change in performance, it is
difficult to predict the actual performance without any experimental
data.
The addition of a throttling valve to hold grey water in the drain tank
at all times will certainly improve performance. Again without
experimental data, it is hard to predict the actual effect of adding a
throttling valve.
Finally, the largest change in actual savings vs. the predicted values
will come from the hot water usage habits of the occupants using the
system. The predictions above were made for equal grey water and cold
water flow (i.e. only the shower is running, nothing else). In reality
if someone is using hot water (anywhere in the building) while the
shower is running, additional savings will be seen. For a normal house
this is usually not a concern, because most families will not wash
dishes while someone is taking a shower. But in a building with four or
eight different apartments, it will be very common for someone to be
washing dishes while another apartment is using the shower. It is hard
to quantify this savings without knowing exactly when people will use
hot water.
Economic Savings
The
prediction of economic savings largely depends upon the energy savings
predictions. As stated before it is very difficult to predict accurate
energy savings, but we will use our previous predictions as a base for
this economic analysis. It can be assumed that while these numbers are
not exact, they are at least with in a ballpark figure of actual
savings.
For this analysis, because we do not know the exact total occupancy of
the housing complex, we will calculate savings on a per person basis.
Using the same assumptions as above, we know we have a 4564.8
Btu/shower. Say a person takes an average of 1.25 showers per day and
we have a savings of 5706 Btu/day per person.
To translate this into a monetary value we will use the current
University Park as an example. University Park currently uses natural
gas water heaters. These typically have an efficiency of about 60%. So
9510 Btu/day would need to be used by the current water heater to meet
the output of the grey water heat recovery system. The average cost of
natural gas for the University of Maine is $0.75/therm or
$0.000008/Btu. This translates to the per person savings shown in table
3.2.
Table 3.2. Per Person Savings.
|
Daily
|
$0.071325
|
|
Monthly
|
$2.17
|
|
Yearly
|
$26.03
|
Assuming four showers are connected to one drain, thus an average of
fifteen people are utilizing the grey water heat recovery system, there
will be a monthly savings of $32.55 per system. The GFX system with an
installed cost of $439 will pay for itself within 14 months.
In this case allowing multiple families to share one GFX system makes
this option particularly attractive. Other factors will change the
actual economic savings. Particularly worth noting are rising natural
gas prices. The more expensive natural gas becomes the greater the
savings that will be gained by the GFX system.
This example compares the savings vs. the current University Park,
which relies on natural gas for water heating. The energy efficient
housing complex will rely primarily on solar energy for water heating
and only use natural gas or another fuel for peak demand needs. This
will drastically change the economic savings with the GFX system, since
solar power is essentially free after the initial cost.
Conclusion
The
GFX system offers large savings and a very low initial cost. Final
design sizing, economics, and implementation will depend primarily upon
its interaction with other water heating systems (i.e. solar water
heating). For this reason the final design of the grey water heat
recovery system will have to wait until the solar water system is
designed. However at this time we know the system will be a GFX model,
insulated on the outside, possible containing a throttling valve, and
will be shared by multiple showering units. In addition a similar GFX
system will be placed in the laundry facility.
1 EERE
Consumer’s Guide: Drain-Water Heat Recovery. 12 Sep. 2005. United States Department of Energy, Office
of Energy Efficiency and Renewable Energy. 22 Nov. 2005. <http://www.eere.energy.gov/consumer/your_home/water_heating/index.cfm/mytopic=13040>
2 Graywater
Heat Recovery (DHR) System: GFX. 2005. Waterfilm Energy Inc. 22 Nov. 2005. <http://gfxtechnology.com/contents.html>
3 American Society of Heating, Refrigerating and
Air-Conditioning Engineers. 2003 ASHRAE
Handbook - Heating, Ventilating, and Air-Conditioning Applications - SI
edition. New York: ASHRAE, 2003.